Add details on frequency measurement
This commit is contained in:
parent
d1c605059c
commit
61ba7e6d12
1 changed files with 13 additions and 5 deletions
|
|
@ -122,7 +122,11 @@ Spectrum (DSSS) modulation carried out on grid frequency through a large control
|
|||
After forward error correction and cryptographic verification it re-flashes the meter's main microcontroller over the
|
||||
standard JTAG interface. Note that our modulation technique is \emph{changing the grid frequency itself}. This is
|
||||
fundamentally different in both generation and detection from systems such as traditional PLC that superimpose a signal
|
||||
on grid voltage, but leave the underlying grid frequency itself unaffected.
|
||||
on grid voltage, but leave the underlying grid frequency itself unaffected. The safety reset controller is an
|
||||
off-the-shelf microcontroller much smaller than the one used for the meter's main application controller. It measures
|
||||
grid frequency from a voltage waveform acquired using its internal analog-to-digital-converter (ADC) directly connected
|
||||
to the mains voltage input through a resistive divider chain. The use of an off-the-shelf microcontroller keeps the
|
||||
implementation overhead of our solution very low in both per-unit and engineering cost.
|
||||
|
||||
\begin{figure}
|
||||
\centering
|
||||
|
|
@ -340,6 +344,7 @@ while the public internet and mobile networks are still offline and it is unaffe
|
|||
telecommunication networks.
|
||||
|
||||
\subsection{Characterizing Grid Frequency}
|
||||
\label{grid-freq-characterization}
|
||||
|
||||
In utility SCADA systems, Phasor Measurement Units (PMUs, also called \emph{synchrophasors}) are used to precisely
|
||||
measure grid frequency among other parameters. This task is much more complicated in practice than it might appear at
|
||||
|
|
@ -515,10 +520,13 @@ the meter's display after boot-up.
|
|||
\label{fig_demo_sig_schema}
|
||||
\end{figure}
|
||||
|
||||
Since we did not have an aluminium smelter ready, we decided to feed our proof-of-concept reset controller with an
|
||||
emulated grid voltage sine wave from a computer's headphone jack. Where in a real application this microcontroller might
|
||||
take ADC readings of input mains voltage divided down by a long resistive divider chain, we instead feed the ADC from a
|
||||
$\SI{3.5}{\milli\meter}$ audio input. For operational safety, we disconnected the meter microcontroller from its
|
||||
To measure grid frequency in our demonstrator, we ported the same code we used in
|
||||
Section~\label{grid-freq-characterization} to our demonstrator, again using the voltage measured using the
|
||||
microcontroller's internal ADC but using a regular crystal instead of a crystal oven for the microcontroller's system
|
||||
clock. Since we did not have an aluminium smelter ready, we decided to feed our proof-of-concept reset controller with
|
||||
an emulated grid voltage sine wave from a computer's headphone jack. Where in a real application this microcontroller
|
||||
would take ADC readings of input mains voltage divided down by a long resistive divider chain, we instead feed the ADC
|
||||
from a $\SI{3.5}{\milli\meter}$ audio input. For operational safety, we disconnected the meter microcontroller from its
|
||||
grid-referenced capacitive dropper power supply and connected it to our reset controlller's debug USB power supply.
|
||||
|
||||
We performed several successful experiments using a signature truncated at 120 bit and a 5 bit DSSS sequence. Taking the
|
||||
|
|
|
|||